The PEL 103 is a low cost, simple to use, one, two (split phase) and three phase power/energy data logger. This product is ideal for electricians, engineers and contractors doing work in the area of building and system monitoring and upgrades, as well as residential and overall energy audits. All vital energy data is easily measured, recorded, and analyzed. Reports can be generated with confidence with minimal configuration time and effort (Standard and Customizable Reports supplied).
The instrument’s design enables it to be installed inside a load center panel (including the current sensors) allowing the door to close on most panels. The PEL 100 series offers all the essential functions for logging power/energy data from most electrical power networks in use today across the world (17 network set-ups provided). The PEL 100 series energy loggers measure and record three True RMS voltage inputs and current inputs, Watts, VARS, VA and Energy (kWh and kVA). Power Factor (PF), Displacement Power Factor (DPF), Crest Factor, Frequency and THD are calculated and recorded as well. Individual harmonic % information from 1 to the 50th harmonic are recorded at the operator’s choice. All variables are recorded and stored at a one second interval and on user selectable demand intervals from 1 to 60 minutes.
The PEL 103 comes either with or without sensors, see model options and descriptions below.
Product Features:
- Simple to use, single, dual-split and three phase power and energy logger
- LCD Display
- Three MA193-10-BK Sensors included
- Equipped with four powerful magnets for mounting the instrument on a metallic surface
- 1000V CAT III and 600V CAT IV
- Measurement of RMS voltages and currents at 128 times per cycle and stored every second
- Power Measurements: VA, W and var
- Energy Measurements: VAh, Wh (source load) and varh (quadrant indication)
- Updated features in DataView software for configuring real-time communication with a PC and report generation with pre-defined or user defined templates
- USB, LAN, Ethernet and Bluetooth (Class 1 wireless communication, up to 300 ft. away)
- Minimal programming required
- Satisfies the recommendations of NEC Code 220.87
- Can be configured from front panel, through Dataview control panel or free app
- Power adapter allows the PEL 103 to be powered from a phase measurement input
- Provides all the necessary functions for power and energy data logging for 50Hz, 60Hz, 400Hz and DC distribution systems
- Automatic recognition of the connected current sensors/probes
Applications:
- Measure efficiency, find areas for potential savings
- Track sub-billing occupants for energy costs
- Assign energy costs to departments or operations within a department
- Track peak demand periods and find opportunities for surcharge reductions
- Determine present capacity and circumvent unnecessary electrical expansion costs
- Monitor stray voltages and neutral current
- Verify the reliability and operation of electrical machinery
- Improve response time to solve power related problems
- Track energy availability and reliability of supply
- Reduce field service time at sub-stations
- Baseline studies for system upgrades in high-rise and office buildings
- Remote configurations, monitoring and event loading
Included:
- 1 - Small Classic Tool Bag
- 3 - MiniFlex MA193-10-BK Sensors
- 1 - 5 ft USB Cable
- 4 - Black Test Leads and Alligator Clips
- 1 - Power Cord
- 12 - Color-coded ID Markers
- 1 - Safety Card
- 1 - Sensor Compliance Sheet
- 1 - 2GB SD-Card
- 1 - Quick start guide
- 1 - USB Stick with DataView software
- 1 - User
Inputs
|
3 Voltage / 3 Current: calculation of neutral current
|
Sample Rate
|
128 per Cycle
|
6.4kHz at 50Hz
|
7.68kHz at 60Hz
|
Specification
|
Range
|
Measurement Range
|
Resolution
|
Accuracy (Typical)
|
Volt
|
Vrms
|
1000V P to N
|
10 to 1000V
|
0.1V
|
±0.2% Rdg + 0.2V
|
Urms
|
1000V P to P
|
17 to 1700V
|
0.1V
|
±0.2% Rdg + 0.4V
|
Amps @ 50 and 60Hz
|
Amps (1V nominal)
(excluding clamp accuracy
|
Probe dependent
|
0.2%< I < 120% Inom
|
Probe dependent
|
±0.2% Rdg + 0.02% Inom
|
AmpFLEX & MiniFlex
(including sensor accuracy)
|
Range 100A
Range 400A
Range 2kA
Range 10kA
|
200mA to 120A
5 to 440A
50 to 2400A
400A to 12kA
|
1mA
0.1A
0.1A & 1A
1A
|
±1.2% Rdg + 50mA
±1.2% Rdg + 0.2A
±1.2% Rdg + 1A
±1.2% Rdg + 5A
|
Frequency
|
|
42.5 to 69Hz
|
0.01Hz
|
±0.1Hz
|
Power
|
Watts (VA, var) P-Q-S
|
10W to 10GW / 10var to 10Gvar / 10VA to 10GVA
|
4 digits min
|
±0.5% Rdg + 0.005% Pnom
|
Power Factor (Cos Φ/DPF)
|
-1 to 1
|
0.001
|
±0.05
|
Energy
|
kWh (kVAh, kvarh) P-Q-S
|
Up to 4EWh / 4Evarh / 4 EVAh (E = 1018 )
|
±0.5% Rdg
|
Harmonics
|
DC, 1 to 50
|
Volts & Amp %
|
|
0.01 to 655.0%
|
0.01%
|
±1% Rdg from 1 to 25
|
THD
|
|
0.00 to 655.0%
|
0.01%
|
±1% Rdg
|
General Features
|
Case
|
Design Rugged, shock proof with integrated protective holster, IP54 not included terminals. Shock and vibration IEC61010
|
Interface
|
Isolated USB, Bluetooth, and Ethernet, SD card for direct transfer to PC. Dataview software for real time data, configuration and reporting included
|
Memory
|
8GB SD card (SDHC compliant, FAT32 formatted) 32GB max
|
Display
|
LCD with backlight
|
Real-Time Clock
|
Time and date stamp for Trend mode
|
Power
|
AC 110V/230V 50/60Hz 15VA; Battery backup when power OFF, 60 minutes typical
|
Dimensions (L x W x H)
|
10.08 x 4.92 x 1.46” (256 x 125 x 37mm)
|
Weight
|
2.2lbs (1kg)
|
Altitude Operating
|
2000m (6560ft)
|
Operating Temperature
|
32 to 108.5°F; (0°C to +42.5°C) from 10 to 85% RH
|
Storage Temperature
|
-4 to 122°F; (-20°C to +50°C) from 0 to 75% RH with battery pack
|
Electro-Magnetic-Compatibility (EMC)
|
EN 61326-1 for emission and immunity
|
IP Rating
|
IP54 per IEC 60529
|
Safety
|
IEC/EN 61010-1 (1000V CAT III-600V CAT IV), IEC 1326-1
|
|
|
|