The TRMS Power Clamp-on Meter Model 607 provides a new standard for safety and measurement capability not available in any other clamp meter sold today. Safety Rated at 1000V CAT IV, it is safe to operate in most electrical environments. It is rugged enough for the most demanding work environments and will withstand both dust and water spray with its IP54 rating. It is ergonomically designed and easily used by one hand, including function selection and button pushing even with a glove on. In addition to the standard measurement of volts, amps, frequency, resistance, diode checking and continuity, the Model 607 offers several unequaled functions including: AC, DC and AC+DC volts, amps and power, True InRush®, power measurements, harmonic analysis, data logging, and more.
Model 607 - Cat. #2139.61: Includes hard carrying case, set of (2) color-coded (red/black) silicone insulated test leads, test probes and alligator clips (red/black), Bluetooth USB adapter, (4) 1.5V AA batteries, safety information sheet, and a USB thumb drive supplied with DataView® software and a user manual.
Voltage Range:
|
1000Vrms AC/DC/AC+DC Autoranging
|
Resolution Max:
|
0.01V
|
Current Range:
|
2000Arms AC, 3000ADC
|
Resolution Max:
|
0.01A
|
Accuracy V Typical:
|
1% ± 3cts
|
Accuracy A Typical:
|
1% ± 3cts
|
True InRush®:
|
20 to 2000AAC, 20 to 3000ADC
|
Power Measurement Max:
|
2MW AC, 3MW DC
|
Harmonics:
|
Up to 25th
|
THD:
|
Yes, %f and %r
|
Continuity:
|
Selectable from 0 to 999.9Ω
|
Resistance:
|
100kΩ
|
Frequency:
|
20kHz in V, 2kHz in A
|
Power Factor:
|
Yes
|
MIN/MAX/PEAK-/PEAK+
|
Yes
|
∆REL:
|
Yes
|
Recording:
|
Yes, up to 1000 points (160 hours at 10 min intervals)
|
Communication:
|
Bluetooth
|
Software:
|
Yes, DataView included
|
Power Source:
|
4 x AA, NEDA 15A, IEC LR6
|
Battery Life:
|
>350 hours
|
Dimensions:
|
10.7 x 3.6 x 1.6" (272 x 92 x 41mm)
|
Weight:
|
1.4 lbs (640g) with batteries
|
Jaw Opening:
|
2.36" (60mm)
|
Operating Temperature:
|
-4° to +131°F (-20 to +55°C)
|
Storage Temperature:
|
-40° to +158°F (-40 to +70°C)
|
Operating Humidity:
|
90% up to 131°F (55°C)
|
Pollution Degree:
|
2
|
Ingress Protection:
|
IP54
|
EMC:
|
EN61326-1
|
Safety Compliance:
|
EN/IEC 61010-1 to 1000V CAT IV

EN/IEC 61010-2-030:2010
EN/IEC 61010-032:2002
|
|
|
|