Martel LC100 Loop Calibrator
|
Item Is In Stock
Item Number: LC100
Manufacturer: MARTEL
Mfr. Part Number: LC100
|
Martel LC100 Loop Calibrator ~ 4-20Ma Current Calibrator
The Martel LC100 provides innovative, powerful features to make your calibration job easier. A handful of clearly marked keys provide access to the full functionality of the unit.
-
High accuracy of +-0.015%
-
High resolution of 0.001mA/0.001V
-
% Error Function eliminates manual error calculation
-
Extended Adjustment Range - digital knob and user - selectable decade output allow both large and incremental (0.001 mA step) output changes
-
Reads 0 to 28.0 VDC
-
Built-in 250 Ohm Register facilitates calibration of HART devices
-
Automatic Step and Ramp functions allow for Remote Calibrations
-
Loop Power Measurements
-
Stimulates, Powers and Measures Two-Wire Transmitters
-
Five Push button Preset Outputs (4,8,12,16,20 mA)
-
Fuseless Input Protection up to 250 VAC
-
Includes neoprene sleeve, NIST Certificate with calibration data
-
Compare with other leading Manufacturers
Input: Current: 0.000 to 24.000mA, -25.00 to +125.00%; Voltage: 0 to 28 VDC; Input Protection: fuseless, up to 250 VAC
Output: Source/Stimulate Range: 0.000 to 24.000mA, -25.00 to + 125.00%; Drive Capability: 1200 Ohm without HART rseistor, 950 Ohm with HART resistor; Loop Supply voltage: 24 VDC; Range Select: Decade, Incremental to 0.001 mA steps
Resolution: 1µA
Accuracy: +-0.015% of reading +-2µA
Temperature Range: Operating: -10 to +55C; Storage: -20 to +70C
Power Requirements: Battery: 9V, one required; included; AC adapter optional
Accessories Included: Protective Rubber boot, Test leads, 9V battery, NIST Certificate, and instruction manual ~ Options: Rechargeable battery, AC adapter/charger
|
|
|